YSLY


Flexible PVC Control Cable

Application
  • Instrumentation and control engineering
  • Industrial electronics
  • Measurement and control wiring in machinery
  • Production and assembly lines
  • Dry, damp and wet indoor locations
  • Areas with low mechanical stress
Construction
No Component Material / Description
1 Conductor Class 5 stranded annealed bare electrolytic copper; IEC 60228 / DIN EN 60228 / EN 60228
2 Insulation PVC compound; EN 50363-3
3 Core identification DIN VDE 0293 / TS EN 50334, or black cores with white numbers
4 Stranding Cores laid up in layers with an optimized lay pitch
5 Sheath PVC compound; EN 50363-4-1
6 Sheath colour Grey, RAL 7001
Technical Characteristics
Parameter Value Unit
Operating voltage 300/500 V
Test voltage 2000 V
Insulation resistance 20 MΩ·km
Temperature - mobile -5 to +70 °C
Temperature - fixed -30 to +70 °C
Minimum bending radius 7.5 x cable diameter -
Flame retardant test IEC 60332-1-2
DIN EN 60332-1-2
EN 60332-1-2
-
Electrical Values by Cross-Section
Size (mm²) Conductor resistance (Ω/km) Current capacity (A)
0.5 39 6.0
0.75 26 13
1.0 19.5 16
1.5 13.3 20
2.5 7.98 25
Notes / Type Options
  • Flexible construction facilitates installation in confined spaces. Not suitable for outdoor use.
  • OZ: Black cores, without green/yellow earth core.
  • JZ: Black cores, with green/yellow earth core.
  • OB: Coloured cores, without green/yellow earth core.
  • JB: Coloured cores, with green/yellow earth core.
Marking

ATEK KABLO - YSLY-[Type] - [Cores × Size] - 300/500 V - [Batch No] - [Metre]