LIHCH


Flexible Screened Halogen-Free Control and Signal Cable
HFFR Low Smoke Screened Control Cable

APPLICATION
  • Indoor signal, data and control wiring where electromagnetic interference must be reduced
  • Measurement, instrumentation, process-control and automation circuits
  • Industrial electronics, control cabinets, machinery and plant engineering
  • Computer systems, office equipment and data-processing devices requiring screened signal lines
  • Building communication, intercom, public-address and indoor sound systems
  • Public buildings and high-occupancy areas such as hospitals, schools, airports, malls and transport hubs
  • Fire-safety-sensitive areas requiring low smoke and low corrosive gas emission
CONSTRUCTION
No Component Material / Description
1 Conductor Class 5 stranded annealed bare electrolytic copper acc. IEC 60228, EN 60228 and DIN VDE 0295
2 Insulation Halogen-free HFFR compound acc. EN 50290-2-26
3 Colour Code Core identification acc. DIN 47100
4 Stranding Cores laid up in layers with an optimized lay pitch
5 Separator Tape Polyester (PET) tape
6 Screen Tinned copper braid for EMC protection
7 Sheath Halogen-free HFFR compound acc. EN 50290-2-27
8 Sheath Colour Grey, RAL 7001
9 Type Code OZ: without green/yellow earth core; JZ: with green/yellow earth core
TECHNICAL CHARACTERISTICS
Parameter Value Unit
Operating Temperature -30 to +70 °C
Operating Voltage 0.22 / 0.34 mm²: 250; ≥0.50 mm²: 300/500 V
Test Voltage 0.22 / 0.34 mm²: 1200; ≥0.50 mm²: 2000 V AC
Conductor Resistance (20 °C) 0.22: 79; 0.34: 56; 0.50: 39; 0.75: 26; 1.0: 19.5; 1.5: 13.3; 2.5: 7.98 Ω/km
Insulation Resistance 0.22 / 0.34 mm²: ≥200; ≥0.50 mm²: ≥20 MΩ.km
Mutual Capacitance 0.22 / 0.34 mm²: 110; 0.50 / 0.75 mm²: 120; 1.0: 130; 1.5: 140; 2.5: 150 pF/m
Impedance Approx. 78 Ω
Inductance Approx. 0.65 mH/km
Current Carrying Capacity 0.22: 2.5; 0.34: 4.5; 0.50: 6.0; 0.75: 13; 1.0: 16; 1.5: 20; 2.5: 25 A
Minimum Bending Radius 15 x Cable Diameter -
Flame Retardancy IEC 60332-1-2; DIN EN 60332-1-2; EN 60332-1-2 -
EMC Performance Tinned copper braid screen for electromagnetic compatibility -
Smoke Density IEC 61034-2; VDE 0482-1034-2; EN 61034-2 -
Combustion Gas Corrosivity IEC 60754-2; VDE 0482-754-2; EN 60754-2 -
Halogen-Free Test IEC 60754-1; VDE 0482-754-1; EN 60754-1 -
Flame Propagation IEC 60332-3-24; DIN EN 60332-3-24; EN 60332-3-24 -
STANDARDS
  • IEC 60228 / EN 60228 Class 5
  • DIN VDE 0295 / DIN 47100
  • EN 50290-2-26 / EN 50290-2-27
  • IEC 60332-1-2 / EN 60332-1-2 / DIN EN 60332-1-2
  • IEC 60332-3-24 / EN 60332-3-24 / DIN EN 60332-3-24
  • IEC 60754-1 / EN 60754-1 / VDE 0482-754-1
  • IEC 60754-2 / EN 60754-2 / VDE 0482-754-2
  • IEC 61034-2 / EN 61034-2 / VDE 0482-1034-2
ORDERING INFORMATION
Product Code Description Packaging
ATKLIHCH LIHCH Flexible Screened Halogen-Free Control and Signal Cable 500 / 1000 m / Drum
MARKING

ATEK KABLO - LIHCH - [Core x Cross-section] - [Voltage] - DIN 47100 - IEC 60332-1-2 - IEC 60754 - IEC 61034 - [Batch Number] - [Meter Mark]

NOTES
  • Overall tinned copper braid supports EMC performance and helps reduce external electromagnetic interference on signal/control lines.
  • Halogen-free HFFR insulation and sheath support low smoke and reduced corrosive gas emission in fire conditions.
  • Suitable for fixed or limited-flexible indoor signal/control wiring in dry or damp interiors; not designed for outdoor exposure or direct burial.
  • LIHCH-OZ: without green/yellow protective conductor; LIHCH-JZ: with green/yellow protective conductor.


Atek Kablo